Loading...
DE EN


PCB current transformers

FEATURES
  • Fully encapsulated
  • Primary to secondary insulation 2.5 kV AC
  • Operating temperature range: -40° C to +120° C
  • Place of manufacture is certi ed according to ISO 9001:2008 / 14001:2004
  • Fully RoHS compliant
  • More details on request or in the single data sheets

PCB current transformer

Iprim 1 - 100 A, 50 / 60 Hz, HV 2,5 kV (prim - sec)
Part NumberCurrent [A]Output Voltage @ Imax Tolerance ± 10%Load Resistant [Ω]
L01-62001-1033.3mV50
L01-62011-2058.3 mV50
L01-62021-3055 mV220
L01-62035-50100 mV220
L01-62045-75119.5 mV220
L01-62055-100128 mV220

PCB current transformer

Iprim 1 - 200 A, 50 / 60 Hz, HV 2,5 kV (prim - sec)
Part No.Ip AmpsTurns RatioTerminating ResistorDCR (Ω)RCFVolts/Amp @rated lp for various loads (Ω)lexVex
OhmsWattNominal@ 10%1005002K5KuArmsVrms
L01-621051.000:11000.002541.801.0100.100.461.432.012370.66
L01-6211101.000:11000.010041.801.0100.100.451.101.423861.32
L01-6212151.000:11000.023041.801.0100.100.450.901.125131.99
L01-6213201.000:11000.040041.801.0100.100.430.760.936282.65
L01-6214251.000:11000.063048.001.0200.100.471.061.315663.65
L01-6215301.000:11000.090048.001.0200.100.470.951.166444.38
L01-6216401.000:11000.160049.301.0260.100.460.871.059145.82
L01-6217501.000:11000.250049.301.0260.100.430.760.9010907.28
L01-6218601.000:11000.360024.001.0010.100.440.660.7612507.41
L01-6219751.000:11000.570024.001.0010.100.390.570.6515209.26
L01-62201001.000:11001.000021.301.0010.100.340.500.56174012.00
L01-62211501.000:11002.250011.001.0020.100.370.500.55182016.60
L01-62222001.000:11004.000011.001.0020.100.310.410.45234022.20